- Circuit Breaker (CB): It has capability to close or open electric circuits under load or fault conditions.
- Disconnector (or Isolator): It can close or open electric circuits under no load condition.
- Earth switch: It is used to earth primary conductors for maintenance purposes.
- CB can be opened or closed on no load or full load or fault condition. Therefore, no check is required for disconnector or earth switch status. However, for safety and security of grid, synchronization check is carried out in grids.
- Disconnector should be operated only when load current is not flowing, i.e. CB should be open. Further, if earth switch is closed, closing of disconnector may cause fault. Therefore, before closing disconnector, associated earth switch status needs to be checked.
- Earth switch should be operated only when primary conductor is already de-energized. Therefore, status of associated disconnectors needs to be checked. In case of long transmission lines, that may be charged from remote end, status of remote end switchgear may not be available. In this case presence of voltage can be checked for interlocking.
- 189A can be operated when: 152 is open, Bus earth switch is open
- 189B can be operated when: 152 is open
- 289A can be operated when: 252 is open, Bus earth switch is open
- 289B can be operated when: 252 is open
- Bus earth switch can be operated when: 189A is open, 289A is open
Disconnector 389A can be operated when:
- CB 352 is open
- Earth switch 389AE and 389BE is open
- Bus-2 Earth switch is open
- CB 352 is open
- Earth switch 389AE and 389BE is open
- CB 352 & CB 252 is open
- Earth switch 389LE is open
- Disconnector 389A & 389B is open
- Disconnector 389A & 389B is open
- Disconnector 389L should be open
- There should be no voltage in line
No comments:
Post a Comment