- Pulse Per Minute (PPM)
- Inter-range instrumentation group timecode-B (IRIG-B)
- Simple Network Time Protocol (SNTP)
- Precision Time Protocol (PTP)
All about electrical engineering, power system, protection relays, protection schemes
Search This Blog
13 March 2022
Time synchronization
Controlled switching
Introduction: In AC system, magnitude of current and voltage signal are always varying in time domain. Whenever opening command is given to a circuit breaker (CB), there may be some current flowing depending on the instant of contact separation. Magnitude of this current will be different for three phases, as they will be passing through different position (angle) at any point.
CB will quench the arc at next current zero. The duration of arc will depend on position of current wave at the moment of separation. As we know, longer the duration of arc, larger the heat generated and larger the contact deterioration. Therefore, best time of opening instant will be just before the current zero to reduce arcing time. Opening at exact current zero will not work due to the reason that the speed of contacts will be slow and recovery voltage across contacts will be larger than dielectric strength gained. This will result in to restrike across contacts and arc will be quenched at next current zero (another 10ms for 50Hz system). Further there may be open time variation due to mechanical reasons in CB for each operation.
Controlled Switching Device (CSD): EHV class CBs, which are electrically ganged, have different operating mechanism for each CB pole. CSD device is used to operate all three CB poles at different times so that arcing in each phase is minimum.
For proper operation of CSD, CB mechanical opening time for each phase is to be measured and entered in to CSD relay. As shown in image below, delay of 3.3ms (for 50Hz system) is to be provided for achieving opening of all phase just before current zero.
CSD is used only for manual operation due to added delay in opening. Protection trip will be issued to CB directly without and controlled switching.
- Reactor opening: to avoid current chopping
- Transformer charging: to avoid high inrush current
- Capacitor charging: to avoid high inrush current
- Transmission line charging: to avoid switching voltage surges
Floating DC system and DC earth fault relay
- Switching off feeders one by one.
- Using DC earth fault locator instrument, which inject low voltage low frequency signal of ~5Hz in DC system. Faulty feeder is identified by measuring leakage current using tuned clamp on meters.
06 March 2022
Interlocking schemes
- Circuit Breaker (CB): It has capability to close or open electric circuits under load or fault conditions.
- Disconnector (or Isolator): It can close or open electric circuits under no load condition.
- Earth switch: It is used to earth primary conductors for maintenance purposes.
- CB can be opened or closed on no load or full load or fault condition. Therefore, no check is required for disconnector or earth switch status. However, for safety and security of grid, synchronization check is carried out in grids.
- Disconnector should be operated only when load current is not flowing, i.e. CB should be open. Further, if earth switch is closed, closing of disconnector may cause fault. Therefore, before closing disconnector, associated earth switch status needs to be checked.
- Earth switch should be operated only when primary conductor is already de-energized. Therefore, status of associated disconnectors needs to be checked. In case of long transmission lines, that may be charged from remote end, status of remote end switchgear may not be available. In this case presence of voltage can be checked for interlocking.
- 189A can be operated when: 152 is open, Bus earth switch is open
- 189B can be operated when: 152 is open
- 289A can be operated when: 252 is open, Bus earth switch is open
- 289B can be operated when: 252 is open
- Bus earth switch can be operated when: 189A is open, 289A is open
Disconnector 389A can be operated when:
- CB 352 is open
- Earth switch 389AE and 389BE is open
- Bus-2 Earth switch is open
- CB 352 is open
- Earth switch 389AE and 389BE is open
- CB 352 & CB 252 is open
- Earth switch 389LE is open
- Disconnector 389A & 389B is open
- Disconnector 389A & 389B is open
- Disconnector 389L should be open
- There should be no voltage in line